heading

PersonalSource™ Desktop UPS
1500 VA, 2000 VA and 3000 VA

PersonalSource UPS Front Views   •   True On-Line Design
  •   Input Power Factor Correction
  •   Built-in Surge Protection
  •   Microprocessor Control &  Communications
  •   Compact size, lightweight
  •   Wide input voltage window
  •   High Efficiency
  •   Over crest ratio indicator
  •   RS232 Communications
  •   Site Wiring Fault indicator
  •   Green Mode Operation
  •   Compatible with generators
  •   Optional internal SNMP/HTTP
  •   Optional Extended Battery Time
  •   Optional Frequency Conversion

 

 

 

 

PersonalSource 600 to 3000 VA Front Views

True On-line Design

A recent Bell Laboratories study indicates that blackouts account for less than 5% of power disturbances. The other 95% consist of surges, noise, sags and brownouts. Equipment connected to utility power experiences an average of 128 such events each month. These events can disrupt proper operation of sensitive computer based equipment, decreasing productivity and creates unnecessary production, service and data recovery costs.

A True On-line UPS is the only design that can provide the maximum protection against major power problems. This is accomplished through converting the incoming AC utility voltage to a DC voltage. From this DC voltage, an AC voltage is then completely regenerated by the UPS, providing a clean, well-regulated source to your equipment, thereby eliminating power related problems. This solidstate generator sets the True Regenerative On-Line UPS apart from all other Line-interactive and Off-line designs, which leave your sensitive equipment connected directly to the dirty utility power 99+% of the time. If your equipment is operating in a “Mission Critical” application, then you need a True On-line UPS and the PersonalSource is the best choice in True On-line UPS technology.

Input Power Factor Correction

All PersonalSource Series models include state of the art Input Power Factor Correction. This greatly reduces the amount of current demanded from your building wiring system, yielding an efficient,  “building friendly” UPS.

Microprocessor Control

The PersonalSource UPS incorporates advanced microprocessor technology. This technology makes possible a high level of internal UPS control as well as system information, data logging, self-diagnostics, SNMP and enhanced computer communication through any RS-232 port.

SNMP/HTTP Remote Management Support

An optional SNMP/HTTP Agent board is available for direct installation into all PersonalSource models. The SNMP/HTTP Agent provides for direct connection of the UPS to any 10Base2 or 10BaseT Ethernet LAN.  

Overall, the PersonalSource Series is uniquely qualified for critical systems combining advanced modular design features with highly reliable construction.

Technical Specifications:

PART NUMBER:

ETI0015
-1505

ETI0015
-15151

ETI0015
-1506

ETI0015
-15161

ETI0015
-1507

ETI0015
-15171

INPUT

Nominal Voltage:

120 VAC

230 VAC

120 VAC

230 VAC

120 VAC

230 VAC

Voltage Range:

87-140 V

170-255 V

87-140 V

170-255 V

87-140 V

170-255 V

Current (max):

11 A

5.9 A

14 A

7.6 A

21 A

11.6 A

Frequency:

50/60 Hz ±5%

Efficiency:

>86%

Power Factor:

>0.95

OUTPUT

VA Rating:

1500 VA

2000 VA

3000 VA

Power5

1050 W

1400 W

2100 W

Voltage
(selectable):

110 VAC

220 VAC

110 VAC

220 VAC

110 VAC

220 VAC

115 VAC

230 VAC3

115 VAC

230 VAC6

115 VAC

230 VAC6

120 VAC3

240 VAC

120 VAC6

240 VAC

120 VAC6

240 VAC

Frequency:

50/60 Hz (auto tracking)

Voltage Regulation:

±2%

Frequency Stability:

±0.3% (Battery mode)

Step Load Change:

±7% for 100% load variation

Harmonic Distortion:

Linear Load            <3%
Non-linear Load     <5%

Overload:

105% load for 50 seconds

Crest Ratio:

3:1

BATTERY3

DC Voltage:

72 VDC

96 VDC

Type:

Maintenance Free, Valve Regulated, Sealed Lead Acid, Flame Retardant, Absorbed Electrolyte

Backup time

Full Load
Half Load

11 minutes typically
30 minutes typically

7 minutes typically
20 minutes typically

5.5 minutes typically
15 minutes typically

Recharge Time:

8 Hours to 90%

Transfer Time

Line Fails/Recovers:

Zero time – true online, no transfer for brownout or blackout

UPS - Bypass/Reverse:

<4 ms for bypass transfers

After Overload:

Auto Transfer to UPS

Audible Noise

@ 1 Meter

<55 dBA

Indicators

LEDs:

Line, Inverter, Battery Reserve, Load, Bypass, Alarm, Crest, Battery & Load Capacity Level

Audible Alarms

 

DC Mode, Low Battery, Over/Under Voltage, Over/Under Frequency, High Temperature, Over Load, Alarm.

Interface

Computer:

UPS industry style RS-232

Environment

Temperature:

0°C – 40°C (32°F – 104°F)

Humidity:

10% - 95% Non-condensing

Mechanical

Input Line Cord:
     120 VAC version
     230 VAC version

6 Foot Cord with
NEMA 5-15P Plug

6 Foot Cord with
NEMA 5-20P Plug

6 Foot Cord with
NEMA L5-30P Plug

6 Foot Cord with
“Schuko” Style Plug

6 Foot Cord with
“Schuko” Plug

6 Foot Cord with
“Schuko” Plug

Output Receptacles:
     120 VAC version
     230 VAC version

(6) NEMA 5-15R

(6) IEC320

Weight

68.4 lbs (31kg)

68.4 lbs. (31kg)

81.4 lbs. (37kg)

Dimensions   Inches:
     H x D x W      (mm)

13.8 x 7.6 x 18.9
(350 x 193 x 480)

 13.8 x 7.6 x 18.9
(350 x 193 x 480)

13.8 x 7.6 x 18.9
(350 x 193 x 480)

Approvals

Agency:

UL, CUL, FCC Class A  (CE on specified models only)