Part Number: ETI0001-1455
Ultra Compact Rugged Industrial 4000 VA
Integrated Rackmount UPS and Intelligent
Power Distribution Unit Combination
P/N:
ETI0001-1455, Raytheon / Industrial Standard,
Ultra Compact PowerStation™ Isolated
Industrial UPS,
4000 VA Rugged Rack Mount UPS w/ PFC, Drawout Battery and
Integrated 6 Circuit, Intelligent, Solidstate Power Distribution Unit
P/N: ETI0001-
Rugged Industrial UPS and PDU Standard Front
Panel Layout w/ Drawout Battery Module
P/N: ETI0001- Rugged Industrial UPS and PDU
Standard Rear
Panel Layout
Optional P/N: ETI0001-0876 UPS and PDU Remote Control Panel in 1U
The field proven PowerStation™ UPS line is ideally suited for
industrial, computer and telecommunications applications requiring high reliability,
rugged construction, compact size and light weight design. These units are
equally suited for use in fixed locations with controlled or uncontrolled
environments. The ETI0001-1455 does not require a separate PDU
since the PDU functions are already integrated into the UPS module. This saves
rack space, cabling and expense while improving overall reliability.
This heavy-duty chassis occupies only 4U (7.0") of rack space while
accommodating a front drawout, hot-swap battery module. The chassis has rounded
metal corners and rugged handles, both front and rear, aiding in safe handling. Internally, all major components are well secured and electrically insulated to prevent
damage due to shock and vibration in any axis. These units can be mounted
horizontally or vertically.
The internal shielded
input transformer provides galvanic isolation with provisions for domestic (115
VAC, CONUS)
and optional autoranging international input voltages (85-270 VAC,
OCONUS).
The
unit also operates as a frequency converter, taking 46-70 hertz input and
converting it to 60 hertz power.
Special EMI/RFI filters and input
power factor correction minimize both input current and harmonics. The input
circuit breaker and the galvanic isolation transformer
all provide a double pole isolated source for shipboard systems or
overseas locations where phase references and grounding are not consistent.
The LED arrays keep the operator informed as to
the unit's status including load and battery levels. The high intensity audible alarm can
be heard in high noise environments.
All controls and protective devices are brought to front and rear panels with critical
switches having finger guards. Further, all front panel devices are recessed to prevent
damage or accidental operation. The internal intelligent PDU allows control of
the individual output circuits incorporating thermal and interlock interfaces
for additional control and safety, plus battleshort override. The display and
control panel can be mounted remotely in the rack at eye level, or on the keyboard console,
or on the unit front panel with only a logic level cable connection.
The rear panel provides locking
connectors for the input and output power with various optional configurations
available. The output connectors are Hubbell 7487 twist lock which use a very
shallow depth mating plug. This reverse air flow version draws air through the front and exhausts out the rear
vents into the rack. A removable and washable intake air filter and high capacity
stainless steel ball
bearing fans provide added protection in both controlled and hostile environments. The "ETI0001-" has the added benefit of having a
field replaceable battery via a front drawout battery module.
The batteries are maintenance free with immobilized electrolyte and are
constructed of flame retardant materials. For more information, see the Battery
Technology section. A
frequency selection switch is available for those sites requiring 50 hertz output instead
of the standard 60 hertz. The Status connector provides an
interface with optional computer software providing loss of AC and low battery status as well as
remote shut down capability. The PDU Remote Control connector provides an
interface to optional remote display/control panels.
See the Power Distribution Units section for a listing of
stand alone PDUs. See the N3 Series UPS section for UPS without
the integrated PDU and remote control.
Overall, the PowerStation line is uniquely qualified for critical shipboard, vehicle,
airborne or land based systems combining advanced modular design features with highly
reliable construction
Technical Specifications: P/N:
ETI0001-1455
AC OUTPUT |
Output voltage: |
120 VAC true sinewave standard,
others optional |
Output rating: UPS |
4000 VA standard in 4U chassis
x 26" deep
0.65 to 0.75 pf std, optional configurations to 24,000 VA |
Non-linear load capacity: |
Up to 100% non-linear load capability w/o
derating |
Output voltage regulation: UPS |
± 3.0% static regulation of nominal
± 4.0% dynamic (0 to 50% load step) |
Overload surge capacity: |
110% for 10 minutes; 125% for 30 seconds |
Harmonic distortion: |
Less than 5.0% into 100% non-linear load |
Output frequency: UPS |
60 or 50 Hz ± 2.5% synchronized to utility
60 or 50 Hz ± 1.0% w/ utility not available
400 or 1000 Hz output available as an option |
Operational status |
Status, load and battery level LEDs,
w/contacts
Adjustable level,+90 dB audible alarm w/on/off |
AC INPUT |
Input voltage selection: |
Nominal 115 VAC, optional
autoranging input of 85-270 VAC |
Input voltage tolerance: UPS |
85-135 VAC @ full load without
using battery, to 70 VAC @ 75% load |
Input frequency: |
From 46 Hz to 70 Hz standard,
optional to 440 Hz |
Input power factor: |
Better than 99% typically |
Input/output isolation: |
4000 VA, up to 120 dB common mode,
1.0 mA leakage |
Input transient suppression: |
Complies with IEEE 587 and UL 1449 |
Input control/protection: |
Guarded 2 pole input breaker w/ UPS fuses
Optional cold start to turn on w/o AC present |
Input power connection: |
Special D shell w/5 high current pins, locking,
shallow depth mating plug |
INTERNAL BATTERY |
Internal battery type: |
Maintenance free immobilized electrolyte,
Flame retardant materials, Oxygen Index 28+ |
Internal battery life: |
Rated for continuous service life of 5 years |
Internal DC protection: |
Panel mounted fuses
standard, breaker optional |
Internal battery replacement: |
Drawout module from rear of unit |
External battery expansion: |
Up to 24 hours w/ optional Battery Expansion Modules |
DISTRIBUTION PANEL |
Output circuits: |
Seven controlled outputs via solidstate
relays |
Output control: |
Local/remote control panel w/rocker switches
Thermal and remote interlock ON/OFF control |
Output receptacles: |
Hubbell 7487 twist locking,
shallow depth mating plug |
MECHANICAL |
Dimensions ( H x D x W ): UPS |
7.0 (4U) x 26.0 x 19.0 in
(178x660x483mm) |
Rack Slide Mount Patterns: |
Jonathan, General Devices patterns
standard, others optional |
Alternate Mounting Options: |
Table, Wall, Floor, Portable,
Horizontal/Vertical |
Shipping weight: Total
UPS w/o Battery Module
Drawout Battery Module |
170 lb. ( 77 kg) with lift handles
front and rear
104 lb. ( 47 kg) with lift handles
front and rear
66 lb. ( 30 kg) with lift handles front |
Audible noise: |
Less than 47 dB @ 5.0 ft., ANSI "A"
scale |
Cooling type: |
High capacity, positive pressure, forced air |
Cooling air direction: |
Front intake, exhaust to rear |
Air intake filter: |
Washable metal filter media,
others optional |
ENVIRONMENTAL |
Storage temperature: |
-40° to 158° F ambient (-40° to
70° C) |
Operating temperature: |
32° to 113° F ambient (0° to 45° C
),
lower/ higher optional |
Operating humidity: |
0 to 95% relative humidity (non-condensing) |
Storage elevation: |
Up to 40,000 ft (12,192 m) |
Operating elevation: |
Up to 10,000 ft (3,048 m), higher
optional |
STANDARDS |
United States: |
Meets UL-1778 standard for UPS equipment,
MIL STDs 167-1, 454, 810, 901D Grade A, 1399-300A & 2000 |
Canada: |
CSA C22.2 No. 107 UPS safety requirements |
EMI Protection: |
EMI/RFI FCC Part 15, Class A;
EN55022; MIL
STD 461 |
OPTIONAL ACCESSORIES |
|
Autoranging International Input, Cold Start, Alternate I/O Configurations, Dual Source
Input, Battery Expansion, Batteryless Operation, Battery
Charger/Conditioner, Power Distribution Units, Software
Interface, Asynchronous serial
COM port, 10BaseT Ethernet SNMP/HTTP port,
Transport Cases, Slides
and Mounting Kits |
This page was last modified on:
May 04, 2008
|