Part Number: ETI0001-1473A
Rugged
COTS 2000VA Combination Integrated
Rackmount Electronic Power Conditioner/UPS
and Intelligent Power Distribution/Controller Unit
FAA
WAAS Rugged COTS
Product
Direct Replacement for 208 VAC
PDT NPM-2000 w/ Transformer Module
Ultra Quiet 2000 VA Rack Mount, Electronic
Power Conditioner
w/ Integrated
3 Circuit, Intelligent, Solidstate Power Distribution Unit
Both Local and Remote Load Control Either Via Hardware or
Software
Both 120 and 208 VAC Outputs,
Elapsed Time Meter, Temperature Alarms
Automatic Load Shedding and Power Up Sequencing
Can Operate as a UPS with Addition of Optional Battery
Module

P/N: ETI0001-1473A 208
VAC
Integrated Power Conditioner
and Power Controller, Standard Front Panel Layout

P/N: ETI0011-1073
208 VAC Transformer Module
Standard Front Panel Layout

P/N: ETI0001-1473A 208
VAC
Integrated Power Conditioner
and Power Controller, Standard Rear Panel Layout

P/N: ETI0011-1073
208 VAC Transformer Module
Standard Rear Panel Layout
The field proven PowerStation™ UPS line is ideally suited for
commercial,
industrial, computer and telecommunications applications requiring high reliability,
rugged construction, compact size and light weight design. These units are equally
suited for use in field deployed or fixed locations with controlled or uncontrolled
environments. The ETI0001-1473A was specifically designed to meet the stringent
requirements of
FAA programs including WAAS.
The ETI0001-1473A does not require a separate PDU since the PDU
functions are already integrated into the UPS module. This saves rack space, cabling and
expense while improving overall reliability.
The heavy-duty chassis, occupying only 5.25”
(3U) for the electronics and 208 VAC transformer modules by 22” depth,
delivers up to 2000 VA of clean, uninterruptible power. The
rounded metal corners and rugged handles, both front and rear, aid in safe
handling. Internally, all major components are well secured and electrically
insulated to prevent damage due to shock and vibration in any axis.
Utilizing the 208 VAC Transformer Module, the unit
accepts domestic
voltages from 170-270 VAC at full
load. At loads less than full load, the input voltage
can be even lower. The input
circuit breaker and the galvanic isolation transformer
provide a double pole isolated source for
overseas locations where phase references and grounding are not consistent.
The
unit also operates as a frequency converter, taking 46-70 hertz input and
converting it to 60 or 50 hertz power
switch selectable. The unit can also be ordered with
46-440 hertz input.
Special EMI/RFI filters and input
power factor correction minimize both input current and harmonics.
The LED arrays keep the operator
informed as to the unit's status including load and battery levels.
The Elapsed Time Indicator records the number of operational hours for records
and scheduling preventative maintenance of attached equipment.
The front and rear panels also provide easy access to both the AC Input and
Battery Input fuses. Coupled with the adjacent spare fuses, MTTR is reduced to
less than 15 minutes.
The internal intelligent thermal
sensors provide two stage monitoring of unit temperatures,
with both local and
remote Inhibit Over Temperature (INHIBIT OVRTMP) capability of thermal shutdown.
INHIBIT OVRTMP can be
engaged via the front panel control, via a remote contact input or via a
software command. When in INHIBIT OVRTMP, an audible alarm is sounded and an
indicator is lit. The high intensity audible alarm can be heard
in high noise environments and includes an audible enable/disable/reset
switch and an adjustable vane to control the sound level.
All controls and protective devices are brought to the front and rear panels
with critical switches or breakers guarded. Further, all front panel devices are
recessed to prevent damage or accidental operation. The internal intelligent PDU
allows control of the individual output circuits incorporating thermal and
interlock interfaces for additional control and safety. Ten push/pull
circuit breakers provide both circuit protection and manual controls. Both the
input and load circuit breakers are shock rated to over 100 Gs. The display and
control panel can be mounted remotely in the rack at eye level, or on the keyboard console,
or on the unit front panel with only a logic level cable connection.
The rear panel provides locking connectors for the input and output power
with various optional configurations available. This
unit draws air through the front air filter and exhausts out the rear vent into the rack.
This allows the unit to be used in either negative or neutral pressure
racks. The stainless steel ball bearing fan is a special extra quiet version to keep the unit's overall
audible level below 44 dB.
The
Status connector provides an
interface with optional computer software providing
loss of AC and low battery status as well as remote shut down capability.
The UPS Remote Control and PDU Remote Control connectors provide an
interface to optional remote display/control panels. The RJ45 LAN port provides an SNMP/HTTP interface for
various UPS parameters and control of the load outputs.
Internal software functions include the ability to Sequence Loads of Startup and
to Shed Loads for either Overload, or Overtemperature or to lengthen battery run
time (when used with battery modules). These functions follow a user defined
priority lists and schedules.
The batteries in the optional battery modules are maintenance free with immobilized electrolyte and are
constructed of flame retardant materials. For more information, see the Battery
Technology section.
See the Power Distribution Units section for a listing of
stand alone PDUs. See the N3 Series for a
version of UPS without the integrated PDU and remote control.
Overall, the PowerStation line is uniquely qualified for critical systems combining advanced modular design
features with highly reliable construction.
Technical Specifications: ETI0001-1473A
AC OUTPUT -
POWER CONDITIONER |
Output voltage: |
120 VAC true sinewave standard |
Output rating: |
2000 VA, 1500 watt max standard in 3U chassis |
Non-linear load capacity: |
Up to 100% non-linear load capability w/o derating |
Output voltage regulation: |
± 3.0% static regulation of nominal
± 4.0% dynamic (0 to 50% load step) |
Overload surge capacity: |
110% for 10 minutes; 125% for 30 seconds |
Harmonic distortion: |
Less than 5.0% into 100% non-linear load |
Output frequency: |
60 or 50 Hz ± 2.5% synchronized to utility
60 or 50 Hz ± 1.0% w/ utility not available
400 or 1000 Hz output available as an option |
Operational status |
AC Input status, UPS operational,
UPS alarm, Battery level, Low battery, Load level, Overload, Warm
temperature, Hot temperature and Battleshort LEDs, Elapsed time hour meter
Alarm contacts for Loss of AC and Low Battery
90+ dB audible alarm with audible on/off/reset switch
Asynchronous serial COM port, 10BaseT Ethernet SNMP/HTTP port, |
AC OUTPUT
- 208 VAC TRANSFORMER MODULE |
Output voltage: |
208
VAC true sinewave standard |
Output rating: |
2000 VA, 1500 watt max standard in 3U chassis |
Non-linear load capacity: |
Up to 100% non-linear load capability w/o derating |
Output voltage regulation: |
± 3.0% static regulation of nominal
± 4.0% dynamic (0 to 50% load step) |
Overload surge capacity: |
110% for 10 minutes; 125% for 30 seconds |
Harmonic distortion: |
Less than 5.0% into 100% non-linear load |
Output frequency: |
60 or 50 Hz ± 2.5% synchronized to utility
60 or 50 Hz ± 1.0% w/ utility not available |
AC INPUT -
208 VAC TRANSFORMER MODULE |
Input voltage selection: |
Nominal 208 VAC |
Input voltage tolerance: UPS |
170-270 VAC @ full load without
using battery,
Down to 140 VAC @ 75% load |
Input frequency: |
From 46 Hz to 70 Hz standard,
optional to 440 Hz |
Input power factor: |
Better than 99% typically |
Input/output isolation: |
2000 VA, up to 120 dB common mode,
w/ 1.0 mA leakage |
Input transient suppression: |
Complies with IEEE 587, UL 1449 and
Mil Std 1399 |
Input control/protection: |
Guarded 2 pole 100 G shock rated
circuit breaker (CB1) |
Input power connection: |
NEMA L6-30P
locking |
AC INPUT -
POWER CONDITIONER |
Input voltage selection: |
Nominal 115 VAC |
Input voltage tolerance: UPS |
85-135 VAC @ full load without
using battery,
Down to 70 VAC @ 75% load |
Input frequency: |
From 46 Hz to 70 Hz standard,
optional to 440 Hz |
Input power factor: |
Better than 99% typically |
Input transient suppression: |
Complies with IEEE 587, UL 1449 and
Mil Std 1399 |
Input control/protection: |
Guarded 2 pole 100 G shock rated
circuit breaker (CB1)
plus UPS input fuse (F2),
spare fuse on front
Optional cold start to turn on w/o AC present |
Input power connection: |
NEMA L5-30P
locking |
AC
DISTRIBUTION - POWER CONTROLLER |
Output circuits: |
Three
controlled outputs via solidstate relays |
Output control: |
Local control panel with (3)
Aircraft style
Shock Rated Push/Pull Circuit Breakers
Thermal and remote interlock ON/OFF control |
Output receptacles: |
(1) NEMA
L5-30R and (2) NEMA 5-15R |
AC
DISTRIBUTION - 208 VAC TRANSFORMER MODULE |
Output circuits: |
One
output controlled via Power Controller |
Output receptacles: |
(1) NEMA
L6-20R |
EXTERNAL BATTERY
(Optional) |
Battery type: |
Maintenance free immobilized electrolyte,
Flame retardant materials (Oxygen Index 28+) |
Battery life: |
Rated for continuous service life of 5 years |
DC protection: |
Panel mounted fuse
standard, breaker optional |
Battery expansion: |
Up to 24 hours w/ Battery Expansion Modules |
MECHANICAL |
Dimensions (H x D x W):
Power Conditioner/Controller
Transformer Module
Battery Module (optional) |
5.25 (3U) x 22.0 x 19.0 in (133
x 559 x 483 mm)
5.25 (3U) x 22.0 x 19.0 in (133
x 559 x 483 mm)
3.50 (2U) x 18.5 x 19.0 in (89 x
470 x 483 mm) |
Rack Slide Mount Patterns: |
Jonathan, General Devices patterns
standard,
Others optional |
Alternate Mounting Options: |
Table, Wall, Floor, Portable, Horizontal/Vertical |
Unit weight:
Power Conditioner/Controller
Transformer Module
Battery Module (optional) |
50 lb. (22 kg) with lift
handles front and rear
60 lb. (22 kg) with lift
handles front and rear
55 lb. (25 kg) with lift handles front and rear |
Audible noise: |
Less than 44 dB @ 5.0 ft., ANSI "A" scale |
Cooling type: |
High capacity, negative pressure, forced air |
Cooling air direction: |
Front intake, exhaust to rear,
others optional |
Air intake filter: |
Washable metal filter media, others optional |
ENVIRONMENTAL |
Storage temperature: |
-40° to 158° F ambient (-40° to
70° C) |
Operating temperature: |
32° to 126° F ambient ( 0° to
52° C), lower / higher optional |
Operating humidity: |
0 to 95% relative humidity (non-condensing) |
Storage elevation: |
Up to 40,000 ft (12,192 m) |
Operating elevation: |
Up to 10,000 ft (3,048 m), higher
optional |
STANDARDS |
United States: |
Meets UL-1778 standard for UPS equipment,
MIL STDs 167-1, 454, 810, 901D Grade A, 1399-300A & 2000 |
Canada: |
CSA C22.2 No. 107 UPS safety requirements |
EMI Protection: |
EMI/RFI FCC Part 15, Class A; EN55022; optional MIL
STD 461 |
OPTIONAL ACCESSORIES |
|
Autoranging International Input, Cold Start, Alternate I/O Configurations,
Battery Modules, Battery
Charger/Conditioner, Power Distribution Units, Software
Interface,
Transport Cases, Slides
and Mounting Kits |
This page was last modified on: