Part Number: ETI0001-1241
Rugged 3000 VA 
Rackmount Shallow Depth UPS

Lockheed Martin Radar Systems Standard Product
3.0 kVA UPS Rugged Rackmount
w/ Reduced Depth and Separate Battery Module

ETI0001-1241 Rugged MilSpec UPS Standard Front Panel Layout
ETI0001-1241 Rugged UPS Standard Front Panel Layout

ETI0001-1241 Rugged MilSpec UPS Standard Rear Panel Layout
ETI0001-1241 Rugged UPS Standard Rear Panel Layout

The field proven PowerStation™ UPS line is ideally suited for industrial, computer and telecommunications applications requiring high reliability, rugged construction, compact size and light weight design. These units are equally suited for use in fixed locations with controlled or uncontrolled environments. The "ETI0001-1241" is being used by the Lockheed Martin on Radar projects because of their stringent performance and reliability requirements. 

The heavy-duty UPS chassis, occupying only 7" (4U) of rack space and the Battery Module only 2U. They both are a shallow 18.5" deep, with rounded metal corners and rugged handles front and rear, aiding in safe handling. Internally, all major components are well secured and electrically insulated to prevent damage due to shock and vibration. 

The internal shielded input transformer provides galvanic isolation with provisions for domestic (115 VAC, CONUS) and optionally for international (230 VAC, OCONUS) input voltages. Special EMI/RFI filters and input power factor correction minimize both input current and harmonics. The unit also operates as a frequency converter, taking 46-70 hertz input and converting it to clean, uninterruptible 60 hertz power. The input switch and the galvanic isolation transformer all provide a  double pole isolated source for shipboard systems or overseas locations where phase references and grounding are not consistent. 

The LED arrays keep the operator informed as to the unit's status including load and battery levels. The high intensity audible alarm can be heard in high noise environments. All controls and protective devices are brought to the front and rear panels with critical switches having finger guards. Further, all front panel devices are recessed to prevent damage or accidental operation. Various optional power distribution controls are available which mount on the front panel or remotely. 

The rear panel provides locking connectors for the input and output power. Multiple input and output power panel options are available. Removable and washable air filters and a high capacity stainless steel ball bearing fans provide added protection in both controlled and hostile environments. The exhaust air is diverted out the front vent, with alternate air flow directions optional. The "ETI0001-1241" has the added benefit of having a field replaceable battery via a separate battery module. The batteries are maintenance free with immobilized electrolyte and are constructed of flame retardant materials. For more information, see the Battery Technology section. The Status connector provides an interface with optional computer software providing loss of AC and low battery status as well as remote shut down capability. 

See the Power Distribution Units section for a listing of stand alone PDUs. See the N5 Series ETI0001-1484 for a version of this UPS with an integrated PDU and remote control.

Overall, the PowerStation line is uniquely qualified for critical shipboard, vehicle, airborne or land based systems combining advanced modular design features with highly reliable construction.

Technical Specifications:
P/N: ETI0001-1241

AC OUTPUT
Output voltage: UPS 120 VAC true sinewave standard, up to 600 VAC optional
Output rating: UPS 3000 VA standard in 4U x 18.5" deep
0.65-0.75 pf standard, optional configurations to 24,000 VA
Non-linear load capacity: UPS Up to 100% non-linear load capability w/o derating
Output voltage regulation: UPS ± 3.0% static regulation of nominal
± 4.0% dynamic (0 to 50% load step)
Overload surge capacity: UPS 110% for 10 minutes; 125% for 30 seconds
Harmonic distortion: UPS Less than 5.0% into 100% non-linear load
Output frequency: UPS 60 Hz ± 1.0% independent of input frequency
50, 400 or 1000 Hz output available as an option
Operational status Status, load and battery LEDs, w/contacts
Adjustable level,+90 dB audible alarm w/on/off
AC INPUT
Input voltage selection: Nominal 115 VAC, optional autoranging input of 85-270 VAC
Input voltage tolerance: UPS 85-135 VAC @ full load without using battery, to 70 VAC @ 75% load
Input frequency: From 46 Hz to 70 Hz standard
Input power factor: Better than 99% typically
Input/output isolation: 3000 VA, up to 120 dB common mode, 1.0 mA leakage
Input transient suppression: Complies with IEEE 587 and UL 1449
Input control/protection: Guarded 2 pole circuit breaker w/ fuse
Remote ON/OFF Control Interface
Optional cold start to turn on w/o AC present
Input power connection: MS 3102A-22-2P, 3 pin, threaded locking
External BATTERY
External battery type: Maintenance free immobilized electrolyte,
Flame retardant materials (Oxygen Index 28+)
External battery life: Rated for continuous service life of 5 years
External DC protection: Front panel mounted fuse standard, breaker optional
External battery time: 8+ minutes @ 100% load, 20+ minutes @ 50%
External battery recharge: Recharged to nominal in 8 hours
External battery replacement: Drawout/plug-in module from front of unit
DISTRIBUTION PANEL
Output circuits: One output standard, optional configurations
Output control: Optional remote control panel w/rocker switches
Output receptacles: MS 3102A-22-2S, 3 pin, threaded locking
MECHANICAL
Dimensions ( H x D x W ): UPS
    2U Battery Module
7.0 (4U) x 18.5 x 19.0 in (178 x 470 x 483 mm)
3.5 (2U) x 18.5 x 19.0 in (89 x 470 x 483 mm)
Rack Slide Mount Patterns: Jonathan, General Devices patterns, others optional
Alternate Mounting Options: Table, Wall, Floor, Portable, Horizontal/Vertical
Unit weight: UPS w/o Battery
   2U Battery Module
95 lb. (43 kg) UPS Module with lift handles front and rear
102 lb. (46 kg) Battery Module with lift handles front and rear
Audible noise: Less than 47 dB @ 5.0 ft., ANSI "A" scale
Cooling type: High capacity, positive pressure, forced air
Cooling air direction: Rear intake, exhaust to front, others optional
Air intake filter: Washable metal filter media, others optional
ENVIRONMENTAL
Storage temperature: -40° to 158° F ambient (-40° to 70° C)
Operating temperature: 32° to 126° F ambient ( 0° to 52° C), lower/ higher optional
Operating humidity: 0 to 95% relative humidity (non-condensing)
Storage elevation: Up to 40,000 ft (12,192 m)
Operating elevation: Up to 10,000 ft (3,048 m), higher optional
STANDARDS
United States: Meets UL-1778 standard for UPS equipment,
MIL STDs 167-1, 454, 810, 901D Grade A, 1399-300A & 2000
Canada: CSA C22.2 No. 107 UPS safety requirements
EMI Protection: EMI/RFI FCC Part 15, Class A; EN55022; MIL STD 461 
OPTIONAL ACCESSORIES
Autoranging International Input, Cold Start, Emergency Power Off, Elapsed Time Meter, Alternate I/O Configurations, Dual Source Input, Battery Expansion, Batteryless Operation, Battery Charger/Conditioner, Power Distribution Units, Software Interface,  Asynchronous serial COM port, 10BaseT Ethernet SNMP/HTTP port, Transport Cases, Slides and Mounting Kits