Part Number: ETI0001-1251
|
AC OUTPUT | |
Output voltage: | 120 VAC true sinewave std, up to 600 VAC optional |
Output rating: UPS | 1550 VA, standard in 4U x
19" chassis 0.65-0.75 pf std, optional configurations to 24,000 VA |
Non-linear load capacity: | Up to 100% non-linear load capability w/o derating |
Output voltage regulation: UPS | ± 3.0% static regulation of nominal ± 4.0% dynamic (0 to 50% load step) |
Overload surge capacity: | 110% for 10 minutes; 125% for 30 seconds |
Harmonic distortion: | Less than 5.0% into 100% non-linear load |
Output frequency: UPS | 60 Hz ± 1.0% independent of input frequency 50, 400 or 1000 Hz output available as an option |
Operational status | Status, load and battery (16) LEDs, w/contacts RS-232 asynchronous serial status COM port Adjustable level,+90 dB audible alarm w/on/off |
AC INPUT | |
Input voltage selection: | Autoranging from nominal 115 VAC to 230 VAC |
Input voltage tolerance: UPS | +15% -25%, or 85-135 and 170-270 |
Input frequency: | From 46 Hz to 440 Hz |
Input power factor: | Better than 99% typically |
Input/output isolation: | 2000 VA, 120 dB common mode, 1.0 mA leakage |
Input transient suppression: | Complies with IEEE 587 and UL 1449 |
Input control/protection: | Guarded 2 pole switch (S1) w/fuse (F2) |
Input power connection: | MS 3102A-22-2P, 3 pin, locking |
DC INPUT / INTERNAL BATTERY | |
External DC input: | Nominal 22 to 32 VDC |
External DC control/protection: | Guarded 2 pole switch (S3) w/rear mounted fuse (F3) |
External DC connector: | MS 3102A-24-9P, 2 pin, locking |
Internal battery type: | Maintenance free immobilized electrolyte, Flame retardant materials (Oxygen Index 28+) |
Internal battery life: | Rated for continuous service life of 5 years |
Internal battery protection: | Rear panel mounted fuse (F1) |
Internal battery time: | 10+ minutes @ 1000 watt load, 20+ minutes @ 50% |
Internal battery recharge: | Recharged to nominal in 8 hours |
Internal battery replacement: | Drawout/plug-in module from front of unit |
DISTRIBUTION PANEL | |
Output circuits: | Six outputs standard, optional configurations |
Output control: | Guarded 3 pole switch (S5) |
Output receptacles: | Metal shell NEMA 5-15R, 3 pin locking, other options |
MECHANICAL | |
Dimensions ( H x D x W ): | 7.00 (4U) x19.0 x 19.0 in (178 x 483 x 483 mm) |
Rack Slide Mount Patterns: | Jonathan, General Devices, others optional |
Alternate Mounting Options: | Table, Wall, Floor, Portable, Horizontal/Vertical |
Unit weight: | 98 lb. (45 kg) with lift handles front and rear |
Audible noise: | Less than 47 dB @ 5.0 ft., ANSI "A" scale |
Cooling type: | High capacity, negative pressure, forced air |
Cooling air direction: | Front intake, exhaust to rear |
Air intake filter: | Washable metal filter media, others optional |
ENVIRONMENTAL | |
Storage temperature: | -13° to 140° F ambient (-25° to 60° C) |
Operating temperature: | 50° to 104° F ambient ( 10° to 40° C) |
Operating humidity: | 0 to 95% relative humidity (non-condensing) |
Storage elevation: | Up to 40,000 ft (12,192 m) |
Operating elevation: | Up to 10,000 ft (3,048 m), higher optionally |
STANDARDS | |
United States: | Meets UL-1778 standard for UPS
equipment, MIL STDs 167-1, 454, 810, 901D Grade A, 1399-300A & 2000 |
Canada: | CSA C22.2 No. 107 UPS safety requirements |
EMI Protection: | EMI/RFI FCC, Class A; EN55022; MIL STD 461 |
OPTIONAL ACCESSORIES | |
Autoranging International Input, Emergency Power Off, Elapsed Time Meter, Cold Start, Alternate I/O Configurations, Dual Source Input, Battery Expansion, Batteryless Operation, Battery Charger/Conditioner, Power Distribution Units, Software Interface, 10BaseT Ethernet SNMP/HTTP port, Transport Cases |