Part Number: ETI0001-1237
Model: ETI0001-S1R-KII/2.0
NSN: 6130-01-462-8656 or
NSN: 6130-01-470-8743
TAC-4 P/N:
S5257-00001
Ultra Rugged Industrial 2000 VA
Rackmount Tactical UPS
TAC-4, TAC-JW, Tomahawk, ATWCS and Hewlett Packard Standard
Product
Standard S1 Configuration, PowerStation™ Isolated UPS
Industrial 2000 VA Rugged Rack Mount, Modular Power System

P/N: ETI0001-1237 Rugged Industrial UPS Standard Front Panel Layout
NSN: 6130-01-462-8656 or NSN: 6130-01-470-8743

P/N: ETI0001-1237 Rugged Industrial UPS Standard Rear Panel Layout
The field proven PowerStation UPS line is ideally suited for
industrial, computer and telecommunications applications requiring high
reliability, rugged construction, compact size and light weight design. These
units are equally suited for use in fixed locations with controlled or uncontrolled
environments.
The ETI0001-1237 was
specifically designed to mount in the TAC-4 racks and interface with either the
TAC-4 PDU or any of numerous ETI
PDUs.
The heavy-duty chassis occupies only 5.25" (3U) of rack space while delivering up to
2000 VA of clean, uninterruptible power. The rounded metal corners and rugged handles, aid
in safe handling. Internally, all major components are well secured and electrically
insulated to prevent damage due to shock and vibration. The optional heavy-duty rack slides provide
easy installation and removal of the unit with full extension. Rear shock
isolation/alignment bushings off load the slides when the unit is fully engaged.
The internal shielded
input transformer provides galvanic isolation with provisions for both domestic (115
VAC, CONUS) and international (230 VAC, OCONUS) input
voltages. The input voltage selection switch allows inputting either 115 VAC or 230 VAC
without having to open the UPS enclosure.
Special EMI/RFI filters and input
power factor correction minimize both input current and harmonics.
The LED arrays keep the operator informed as to
the unit's status including load and battery levels. The high intensity audible alarm can
be heard in high noise environments, yet is easily adjustable to suit quieter conditions.
All controls and protective devices are brought to front and rear panels with critical
switches having finger guards. Further, all front panel devices are recessed to prevent
damage or accidental operation.
The rear panel provides locking
connectors for the input and output power with various optional configurations
available. This reverse air flow version draws air through the front and exhausts out the rear
vent into the rack. A removable and washable intake air filter and high capacity
stainless steel ball
bearing fan provide added protection in both controlled and hostile environments.
The batteries are maintenance free with immobilized electrolyte and are
constructed of flame retardant materials. For more information, see the Battery
Technology section. The two
status D shell connectors provide both a contact and serial interface with
optional computer software providing loss of AC and low battery status as well as remote shut down
capability.
See the Power Distribution Units section for a listing of
stand alone PDUs. See the N5 Series ETI0001-1437 for a
version of this UPS with an integrated PDU and remote control
Overall, the PowerStation line is uniquely qualified for critical shipboard, vehicle,
airborne or land based systems combining advanced modular design features with highly
reliable construction.
Technical Specifications:
P/N: ETI0001-1237
NSN: 6130-01-462-8656
or NSN: 6130-01-470-8743
| AC OUTPUT |
| Output voltage: |
120 VAC true sinewave standard,
others optional |
| Output rating: UPS |
2000 VA standard in 3U chassis
0.65-0.75 pf std, optional configurations to 24,000 VA |
| Non-linear load capacity: |
Up to 100% non-linear load capability w/o
derating |
| Output voltage regulation: UPS |
± 3.0% static regulation of nominal
± 4.0% dynamic (0 to 50% load step) |
| Overload surge capacity: |
110% for 10 minutes; 125% for 30 seconds |
| Harmonic distortion: |
Less than 5.0% into 100% non-linear load |
| Output frequency: UPS |
60 Hz ± 1.0% independent of input frequency
50, 400 or 1000 Hz
output available as an option |
| Operational status |
Status, load and battery LEDs, w/contacts
RS-232 asynchronous serial status COM port
Adjustable level,+90 dB audible alarm w/on/off |
| AC INPUT |
| Input voltage selection: |
Nominal 115 VAC or 230 VAC via selection switch (S6) |
| Input voltage tolerance: UPS |
85-135 VAC or 170-270 @ full
load without using battery, to 70 VAC @ 75% load |
| Input frequency: |
From 46 Hz to 70 Hz standard,
optional to 440 Hz |
| Input power factor: |
Better than 99% typically |
| Input/output isolation: |
2000 VA, 120 dB common mode, 1.0
mA leakage |
| Input transient suppression: |
Complies with IEEE 587 and UL 1449 |
| Input control/protection: |
Guarded 2 pole switch (S1) w/fuse (F2) |
| Input power connection: |
MS 3102A-22-2P, 3 pin, locking |
| INTERNAL BATTERY |
| Battery type: |
Maintenance free immobilized electrolyte,
Flame retardant materials (Oxygen Index 28+) |
| Battery life: |
Rated for continuous service life of 5 years |
| DC protection: |
Front panel mounted fuse
standard, breaker optional |
| Battery time: |
15+ minutes @ 100% load, 30+ minutes @ 50% |
| Battery recharge: |
Recharged to nominal in 8 hours |
| DISTRIBUTION PANEL |
| Output circuits: |
One output standard, optional configurations |
| Output control: |
Guarded 3 pole switch (S5) |
| Output receptacles: |
MS 3102A-24-10S, 7 pin locking, other options |
| MECHANICAL |
| Dimensions ( H x D x W ): |
5.25 (3U) x 28.0 x 19.0 in (133
x 711 x 483 mm) |
| Rack Slide Mount Patterns: |
Actron/Jonathan slide pattern, others optional |
| Rack rear alignment pins: |
(2) shock isolation/alignment pin/socket sets |
| Alternate Mounting Options: |
Table, Wall, Floor, Portable,
Horizontal/Vertical |
| Unit weight: |
155 lb. (70 kg) with lift handles front |
| Audible noise: |
Less than 47 dB @ 5.0 ft., ANSI "A"
scale |
| Cooling type: |
High capacity, negative pressure, forced air |
| Cooling air direction: |
Front intake, exhaust to rear,
others optional |
| Air intake filter: |
Washable metal filter media, others optional |
| ENVIRONMENTAL |
| Storage temperature: |
-40° to 158° F ambient (-40° to
70° C) |
| Operating temperature: |
32° to 126° F ambient ( 0° to
52° C),
lower/ higher optional |
| Operating humidity: |
0 to 95% relative humidity (non-condensing) |
| Storage elevation: |
Up to 40,000 ft (12,192 m) |
| Operating elevation: |
Up to 10,000 ft (3,048 m), higher
optional |
| STANDARDS |
| United States: |
Meets UL-1778 standard for UPS
equipment,
MIL STDs 167-1, 454, 810, 901D Grade A, 1399-300A & 2000
|
| Canada: |
CSA C22.2 No. 107 UPS safety requirements |
| EMI Protection: |
EMI/RFI FCC Part 15, Class A;
EN55022; MIL
STD 461 standard |
| OPTIONAL ACCESSORIES |
| |
Autoranging International Input,
Emergency Power Off, Elapsed Time Meter, Cold Start, Alternate I/O Configurations, Dual Source
Input, Battery Expansion, Batteryless Operation, Battery
Charger/Conditioner, Power Distribution Units, Software
Interface, 10BaseT Ethernet SNMP/HTTP port,
Transport Cases |
This page was last modified on: