P/N: ETI0001-11xx
|
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
| AC OUTPUT | |
| >Output voltage: | face="Arial">120 VAC true sinewave std, up to 600 VAC optional |
| >Output rating: UPS | face="Arial">1000, 1550 or 2000 VA in 3U chassis 0.65-0.75 pf std, optional configurations to 24,000 VA |
| >Non-linear load capacity: | face="Arial">Up to 100% non-linear load capability w/o derating |
| >Output voltage regulation: UPS | face="Arial">± 3.0% static regulation of nominal ± 4.0% dynamic (0 to 50% load step) |
| >Overload surge capacity: | face="Arial">110% for 10 minutes; 125% for 30 seconds |
| >Harmonic distortion: | face="Arial">Less than 5.0% into 100% non-linear load |
| >Output frequency: UPS | face="Arial">60 or 50 Hz ± 2.5% synchronized to utility 60 or 50 Hz ± 1.0% w/ utility not available |
| >Operational status | face="Arial">Status, load and battery level LEDs, w/contacts Adjustable level,+90 dB audible alarm w/on/off |
| AC INPUT | |
| >Input voltage selection: | face="Arial">120 VAC, optional up to 600 VAC, up to 440 Hz |
| >Input voltage tolerance: UPS | face="Arial">+15% -25% of nominal input rating |
| >Input/output isolation: | face="Arial">Up to 120 dB electrical noise attenuation |
| >Input transient suppression: | face="Arial">Complies with IEEE 587 and UL 1449 |
| >Input control/protection: | face="Arial">Guarded 2 pole input breaker w/ UPS fuse Optional cold start to turn on w/o AC present |
| >Input power connection: | face="Arial">AMP CPC Type XII locking, various options |
| BATTERY | |
| >Type: | face="Arial">Maintenance free immobilized electrolyte, Flame retardant materials (Oxygen Index 28+) |
| >Battery life: | face="Arial">Rated for continuous service life of 5 years |
| >DC protection: | face="Arial">Front panel mounted fuse, optional breaker |
| >Battery expansion: | face="Arial">Up to 24 hours w/ Battery Expansion Modules |
| DISTRIBUTION PANEL | |
| >Output circuits: | face="Arial">Four controlled outputs w/2 pole solidstate relays |
| >Output control: | face="Arial">Local/remote control panel w/rocker switches Thermal and remote interlock ON/OFF control |
| >Output receptacles: | face="Arial">(4) IEC320-15R w/cord restraints, various options |
| MECHANICAL | |
| >Dimensions ( H x D x W ): | face="Arial">5.25 (3U) x 23.5 x 19.0 in (133x597x483mm) |
| >Rack Slide Mount Patterns: | face="Arial">Jonathan, General Devices or Emcor patterns |
| >Alternate Mounting Options: | face="Arial">Table, Wall, Floor, Portable, Horizontal/Vertical |
| >Shipping weight: | face="Arial">115 lb. (52 kg) with lift handles front and rear |
| >Audible noise: | face="Arial">Less than 47 dB @ 5.0 ft., ANSI "A" scale |
| >Cooling type: | face="Arial">High capacity, positive pressure, forced air |
| >Cooling air direction: | face="Arial">Rear intake, exhaust to front or sides or both |
| >Air intake filter: | face="Arial">Washable filter media, various porosities |
| ENVIRONMENTAL | |
| >Storage temperature: | face="Arial">-13° to 131° F ambient (-25° to 55° C ) |
| >Operating temperature: | face="Arial">32° to 113° F ambient (0° to 45° C ),higher optional |
| >Operating humidity: | face="Arial">0 to 95% relative humidity (non-condensing) |
| >Operating elevation: | face="Arial">Up to 10,000 ft (3,048 m), higher optionally |
| STANDARDS | |
| >United States: | face="Arial">Meets UL-1778 standard for UPS equipment, MIL STDs 810, 454 & 1399 Shock/Vib/Electrical |
| >Canada: | face="Arial">CSA C22.2 No. 107 UPS safety requirements |
| >EMI Protection: | face="Arial">EMI/RFI FCC, Class A, optional MIL STDs 461 |
| OPTIONAL ACCESSORIES | |
| face="Arial">Dual Source Input, Batteryless Operation, Battery Expansion Unit, Automatic Battery Test, Software Interface |
|
This page was last modified on:
January 12, 2008
![]()



The
field proven PowerStation UPS line is ideally suited for industrial and telecommunications
applications requiring rugged rack or table mount and/or portable construction,
high reliability, compact size and light weight design. The heavy duty chassis
occupies only 3U of rack space while delivering up to 2000 VA of clean, uninterruptible
power. The rounded metal corners and rugged handles, both front and rear, aid
in safe handling. The optional mounting kit includes flanges and legs for either
horizontal or vertical positioning. Internally, all major components are well
secured and electrically insulated to prevent damage due to shock and vibration.
An internal transformer bay accommodates the input isolation transformer with
provisions for both domestic and optional international voltages for ratings
up to 3000 VA. The LED arrays keep the operator informed as to the unit's status
including load and battery levels. The high intensity audible alarm can be heard
in high noise environments, yet is easily adjustable to suit quieter conditions.
All controls and protective devices are brought to the front panel with critical
switches or breakers guarded. Further, all front panel devices are recessed to
prevent damage or accidental operation. The display and control panel can be
mounted remotely in the rack or on the front panel with only a logic level cable
connection. The input breaker, isolation transformer, and the solidstate load
relays each provide double pole isolation for shipboard systems.